Rectifiers & D.C. Power Supply Systems
High power rectifier sets for electrolyzers


Main specification
| Parameter name | Value | |||||
|---|---|---|---|---|---|---|
| Nickel
Ni | Copper
Cu | Zink
Zn | Fluorine
F | |||
| Primary voltage, kV | 6 ÷ 35
| |||||
| Rectified current, kA | 12 ÷ 50 | 12 ÷ 50 | 25 ÷ 100 | 6,3 ÷ 25 | ||
| Rectified voltage, V | 200 ÷ 850 | 200 ÷ 450 | 450 ÷ 1000 | 450 ÷ 900 | ||
| Type of rectifier | thyristor | |||||
| Rectification circuit | bridge | |||||
| Pulse number | 12 | |||||
| Cooling of thyristors | – distilled, deionized water
– non – freezing liquid | |||||
| Accuracy of current maintaining, % | 1 | |||||
| Voltage adjustment
coarse fine | no – load, on – load tap changers of transformer
by firing angle of thyristor | |||||
| Power factor (without compensation), not worse | 0,9 | |||||
| Installation | – indoors
– outdoors | |||||
| Ambient air temperature | from - 45 °C to + 45 °C | |||||
Delivery set
- switchgear device 6 – 35 kV;
- rectifier set;
- direct current meter;
- heat exchanging unit: – «water – water»,
– «water – air»,
– «non – freezing liquid – water»,
– «non – freezing liquid – air».
Назад в раздел